Adjust and Function Specification
§ CE38 2nd frequency increase setting (setting range 0.0~10.0%)
(2nd Bob up speed %)
Set the 2nd frequency increase percentage.
§ CE39 3rd frequency increase setting (setting range 0.0~10.0%)
(3rd Bob up speed %)
Set the 3rd frequency increase percentage.
§ CE40 Setting Times of 1st frequency increase (setting range0〜200min )
(1st Bob up speed % time)
Set the time of 1st frequency increase percentage.
When multi-step operation time shorter than CE40, CE37 will be the current frequency
increase order. If CE40=0 it will use CE37 as frequency increase order, no matter what
is the perform time in multi-step function.
§ CE41 Setting Times of 2nd frequency increase (setting range0〜200min )
(2nd Bob up speed % time)
Set the time of 2nd frequency increase percentage.
When multi-step function operation time longer than CE40 and shorter than CE41, the
frequency will increased as CE38. If CE41=0 it will use CE38 as frequency increase
order, no matter what is the perform time in multi-step function.
When multi-step operation time is longer or equal to CE41, it will use CE39 as current
frequency increase order.
§ CE42 1st frequency decrease setting (Setting range 0.0~10.0%)
(1st Bob down speed %)
Set the 1st frequency decrease percentage. The setting is related with current working
speed of inverter. When inverter working under multi-steps function mode(Cd01=7),
and CE47=2, or 3、Cd59=1, short external terminal 3(DOWN) and COM, then the
speed will be
Operation frequency = current steps’ frequency – (current steps’ frequency ×CE42)
§ CE43 2nd frequency decrease setting (Setting range 0.0~10.0%)
(2nd Bob down speed %)
Set the second frequency decrease percentage.
§ CE44 3rd frequency decrease setting (Setting range 0.0~10.0%)