DAAB OUTPUT CARD DB407 INSTRUCTION MANUAL
13
No. Name Range Factory Setting
o330* Alarm if there is an error as congured in o331-o339. e
alarm is activated for at least the time set in this channel.
0.00-9.59 minutes 0.00
o331* Alarm for faulty safety edge. Time as in o330. 0 - 1 0
0 Disabled
1 Constant signal
o332* Alarm for critical error message in display 0 - 1 0
0 Disabled
1 Constant signal
o333* Alarm if stop circuit interrupted 0 - 1 0
0 Disabled
1 Constant signal
o334* Alarm if door open 0 - 1 0
0 Disabled
1 Constant signal
o335* Alarm if door is in mid position 0 - 1 0
0 Disabled
1 Constant signal
o336* Alarm if door is in closed position 0 - 1 0
0 Disabled
1 Constant signal
o337* Alarm if vehicle loop 1 is activated 0 - 1 0
0 Disabled
1 Constant signal
o338* Alarm if vehicle loop 2 is activated 0 - 1 0
0 Disabled
1 Constant signal
o339* Alarm if photocell interrupted 0 - 1 0
0 Disabled
1 Constant signal
o342* Alarm for uncritical error message in display 0 - 1 0
0 Disabled
1 Constant signal
o383 Inversion of contact function for output 1 - 2 1
1 Normally open, NO
2 Normally closed, NC
* = Only when o300 is set to 4.