18
Programmable output 5
No. Name Range Factory Setting
o500 Function of output 1 0 - 4 0
0 Disabled
1 Position indication/Movement/Warning. Signal as congured in o510 – o522
2 Presence detection/Direction sensing. Signal as congured in o591
3 Lock
4 Alarm output Signal as congured in o530 – o542
o510 Open position 0 - 1 0
0 Disabled
1 Constant signal
o511 Mid position 0 - 1 0
0 Disabled
1 Constant signal
o512 Closed position 0 - 1 0
0 Disabled
1 Constant signal
o513 Movement 0 - 4 4
0 Disabled
1 Constant signal in the opening movement
2 Constant signal in the closing movement
3 Constant signal in the opening and closing movement
4 No signal during movement, used in combination with o510, o511 and o512.
o514 Delayed switch-o Switch o aer the specied time For
example to switch o lighting a specied time aer closing
0.00-9.59 minutes 0.00
o520 Warning time before start 0.00-9.59 minutes 0.00
o521 Warning function in combination with o520 1 - 4 2
1 Constant signal before automatic closing
2 Constant signal before park and automatic closing
3 Constant signal before close signal, park and automatic closing
4 Constant signal before all signals
o522 Function during warning time 1 - 2 1
1 Output signal disabled during warning in other output
2 Output signal as congured in o510-o513