DAAB OUTPUT CARD DB407 INSTRUCTION MANUAL
19
No. Name Range Factory Setting
o530* Alarm if there is an error as congured in o531-o539. e
alarm is activated for at least the time set in this channel.
0.00-9.59 minutes 0.00
o531* Alarm for faulty safety edge. Time as in o530. 0 - 1 0
0 Disabled
1 Constant signal
o532* Alarm for critical error message in display 0 - 1 0
0 Disabled
1 Constant signal
o533* Alarm if stop circuit interrupted 0 - 1 0
0 Disabled
1 Constant signal
o534* Alarm if door open 0 - 1 0
0 Disabled
1 Constant signal
o535* Alarm if door is in mid position 0 - 1 0
0 Disabled
1 Constant signal
o536* Alarm if door is in closed position 0 - 1 0
0 Disabled
1 Constant signal
o537* Alarm if vehicle loop 1 is activated 0 - 1 0
0 Disabled
1 Constant signal
o538* Alarm if vehicle loop 2 is activated 0 - 1 0
0 Disabled
1 Constant signal
o539* Alarm if photocell interrupted 0 - 1 0
0 Disabled
1 Constant signal
o542* Alarm for uncritical error message in display 0 - 1 0
0 Disabled
1 Constant signal
o583 Inversion of contact function for output 1 - 2 1
1 Normally open, NO
2 Normally closed, NC
* = Only when o500 is set to 4.