DAAB OUTPUT CARD DB407 INSTRUCTION MANUAL
22
No. Name Range Factory Setting
o630* Alarm if there is an error as congured in o631-o639. e
alarm is activated for at least the time set in this channel.
0.00-9.59 minutes 0.00
o631* Alarm for faulty safety edge. Time as in o630. 0 - 1 0
0 Disabled
1 Constant signal
o632* Alarm for critical error message in display 0 - 1 0
0 Disabled
1 Constant signal
o633* Alarm if stop circuit interrupted 0 - 1 0
0 Disabled
1 Constant signal
o634* Alarm if door open 0 - 1 0
0 Disabled
1 Constant signal
o635* Alarm if door is in mid position 0 - 1 0
0 Disabled
1 Constant signal
o636* Alarm if door is in closed position 0 - 1 0
0 Disabled
1 Constant signal
o637* Alarm if vehicle loop 1 is activated 0 - 1 0
0 Disabled
1 Constant signal
o638* Alarm if vehicle loop 2 is activated 0 - 1 0
0 Disabled
1 Constant signal
o639* Alarm if photocell interrupted 0 - 1 0
0 Disabled
1 Constant signal
o642* Alarm for uncritical error message in display 0 - 1 0
0 Disabled
1 Constant signal
o683 Inversion of contact function for output 1 - 2 1
1 Normally open, NO
2 Normally closed, NC
* = Only when o600 is set to 4.