EasyManua.ls Logo

dacell SM110 - Page 8

Default Icon
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DACELL CO., LTD
http://www.dacell.com
TEL:+82-43-2602242, FAX : +82-43-2602245
8
4. Operating flow chart
--Mount indicator to panel and make connection. (Check AC
POWER 110/220V)
-- Press key(data protection unlock)
-- Set data(high, low, F.S, DP, CAL),refer to 6
--sensor output data ---DIP S/W 1, 2, 3, 4
analog output ---- DIP S/W 5
filter frequency ---- DIP S/W 6, 7, 8
-- Sensor : no load
Press key (auto zero)
---Execute auto calibration.
---Check function(Relay output,analog output, reset, hold, peak).
--Press key(data protection mode)
5. HARDWARE
1) Selection of AC input power
(1) Separate P.C.B from case.
(2) The following label is existed under power transformer
2) Transformation of SAMPLING TIME
15 times/sec (standard).
(1) The following label is existed on the P.C.B
Install and connection
Unlock mode
DATA Input
DIP S/W setting
Auto zero
AUTO CAL
Mode Check
Lock mode setting
110V : connect 1 and 2
110 220 110 connect 3 and 4
220V : connect 2 and 3
15 times/sec : connect 1 and C
15 C 30 30 times/sec : connect 2 and C