28
Confirm following statement.
When the unit operate normally, Sometimes the outdoor unit and indoor unit cannot operate.
!Is the setting temperature proper?
@ Is the unit during 3min. Time delay of compressor.
# During frost prevention of lndoor unit.
$ During dehumidifier mode.
Outdoor Fan and Compressor Do Not Run
Check the voltge between and
of indoor unit terminal
Y
L
Check the voltge between and
of outdoor unit terminal
Y
L
Check the voltge between and
of outdoor unit terminal
Y
L
Check compressor,
outdoor fan motor individually
Check the
connecting wire
Check the
connecting wire
Check the wiring
and voltage
within doors
Rating voltage
under 90%
Rating voltage
under 90%
Rating voltage
under 90%