3 | Specific installer safety instructions
Installer reference guide
16
2MXM-A, 3MXM-A, 4MXM-A, 5MXM-A
R32 Split series
4P600463-5E – 2021.12
DANGER: RISK OF BURNING/SCALDING
DANGER: RISK OF ELECTROCUTION
Piping installation (see
"7Piping installation"[
4
32]
)
CAUTION
Piping and joints of a split system shall be made with permanent joints when inside
an occupied space except joints directly connecting the piping to the indoor units.
CAUTION
No brazing or welding on site for units with R32 refrigerant charge during
shipment.
During installation of the refrigeration system, joining of parts with at least one
part charged shall be performed taking into account the following requirements:
inside occupied spaces non-permanent joints are NOT allowed for R32 refrigerant
except for site made joints directly connecting the indoor unit to piping. Site
made joints directly connecting piping to indoor units shall be of non-permanent
type.
CAUTION
Do NOT connect the embedded branch piping and the outdoor unit when only
carrying out piping work without connecting the indoor unit in order to add another
indoor unit later.
WARNING
Connect the refrigerant piping securely before running the compressor. If the
refrigerant piping is NOT connected and the stop valve is open when the compressor
is run, air will be sucked in. This will cause abnormal pressure in the refrigeration
cycle, which may result in equipment damage and even injury.
CAUTION
Do NOT open the valves before flaring is complete. This would cause refrigerant gas
leakage.
DANGER: RISK OF EXPLOSION
Do NOT start the unit if it is vacuumed.
Charging refrigerant (see
"8Charging refrigerant"[
4
46]
)
WARNING
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If
the refrigerant leaks in the room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the formation of a harmful gas.
Turn OFF any combustible heating devices, ventilate the room, and contact the
dealer where you purchased the unit.
Do NOT use the unit until a service person confirms that the part from which the
refrigerant leaked has been repaired.

Table of Contents

Other manuals for Daikin 4MXM80A2V1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 4MXM80A2V1B and is the answer not in the manual?

Daikin 4MXM80A2V1B Specifications

General IconGeneral
BrandDaikin
Model4MXM80A2V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals