SYSTEM OPERATION
The compressor and condenser fan are energized. The
compressor is connected to the Y terminal of the con-
trol module.
The circulator fan is energized at cool speed after a
cool on delay. The electronic air cleaner will also be
energized.
After the thermostat is satisfied, the compressor is
de-energized and the Cool Mode FanOff Delay period
begins.
Following the 60 second Cool Mode Fan Off Delay
period, the cool circulator and air cleaner relay are
de-energized
MANUAL FAN ON:
On a call for Fan, the G thermostat contacts close
signaling the control module.
The LED will display a solid “GREEN”
When a call for G is received, the control will energize
the circulator in low heat speed after the fan on delay
time expires. The electronic air cleaner will also be
energized at this time.
When the thermostat fan switch is moved to the ON
position, the circulator blower is energized at low heat
speed and the electronic air cleaner is also energized
When the thermostat fan switch is moved back to the
AUTO position, the circulator fan and air cleaner relay
are de-energized and the control awaits a thermostat
call for heat or cool.
Exception: During the Cool “On”delay, the control will
not respond to the fan input. If the fan was called prior
to the call for cool, the circulator will remain ener-
gized during the Cool “On”delay.
If the fan is called prior to a call for heat, the circulator
will remain energized during the entire call for heat
sequence.