EWWD120~540MBYNN
Packaged water-cooled water chillers
4PW22685-1
Operation manual
2
Electrical specifications
(1)
General EWWD 500 520 540
Dimensions HxWxD
(mm)
2000x2672x930
Weight
machine weight (kg)
3034 3150 3346
operation weight (kg)
3156 3281 3485
Connections
chilled water inlet
and outlet
(a)
(inch)
2x 3" (2x 88.9 mm OD)
condenser water inlet
and outlet
(a)
(a) Victaulic
®
coupling
(inch)
2x 3" (2x 88.9 mm OD)
pressure relief valve
condenser
(inch)
4x 1"
Compressor
Type semi-hermetic single screw
Qtyxmodel
2x
ZHA7WSGUYE
1x ZHA7WSGUYE+
1x ZHA9LSGUYE
2x
ZHA9LSGUYE
Speed
(rpm)
2880
Oil type FVC 68D
Oil charge volume
(l)
2x 10
+0.5
–0
10
+0.5
–0
+14
+0.5
–0
2x 14
+0.5
–0
Condensor
Type shell & tube
Qtyxmodel 2x CDEW400
1x CDEW400
1x CDEW450
2x CDEW450
Evaporator
Type brased plate heatexchanger
Qtyxmodel
2x AC250EQ-NP128
1x AC250EQ-NP128
1x AC250EQ-NP162
2x AC250EQ-NP162
(1) Refer to the engineering data book for the complete list of specifications.
Model EWWD 120 180 240 280 360 440 500 520 540
Power supply
Phase
3~
•Frequency (Hz)
50
•Voltage (V)
400
•Voltage tolerance (%)
±10
Unit
Nominal running
current
(A)
48 78 108 118 156 186 216 226 236
Maximum running
current
(A)
76 120 174 184 240 294 348 358 368
Recommended fuses
according to IEC 269-2
(gL)
3x 100 3x 160 3x 200 3x 200 2x 3x 200 3x 200+3x 250 2x 3x 250 2x 3x 250 2x 3x 250
Compressor
Phase
3~
•Frequency (Hz)
50
•Voltage (V)
400
Nominal running current (A)
48 78 108 118 78+78 78+108 108+108 108+118 118+118
Control and fan motor
Phase
1~
•Frequency (Hz)
50
•Voltage (V)
230

Other manuals for Daikin EWWD120MBYNN