6 Configuration
Installation manual
10
FBA35~140A2VEB
Split system air conditioners
4P456962-1C – 2017.04
Master unit: Be sure to connect the wiring when combining with a
simultaneously operating multi-type in group control.
Use separate power only in case of following combination:
1×FBA35A + RXS35L or RXM35M
2×FBA60A + RR100/125B or RQ100/125B
2×FBA71A + RR100/125B or RQ100/125B
4×FBA50A + RZQ200C
3×FBA60A + RZQ200C
3×FBA71A + RZQ200C
2×FBA100A + RZQ200C
4×FBA60A + RZQ200C
2×FBA125A + RZQ200C
EN/IEC 61000‑3‑12 provided that the short-circuit power S
sc
is
greater than or equal to the minimum S
sc
value at the interface
point between the user's supply and the public system.
EN/IEC 61000‑3‑12 = European/International Technical
Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current >16A and ≤75A per phase.
It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a short-circuit power S
sc
greater than or equal to the
minimum S
sc
value.
Ensure that equipment is connected only to a supply with a short-
circuit power S
sc
greater than or equal to S
sc
in table below.
Combination FBA35A FBA50A FBA60A FBA71A
RZAG71M 2 (—) 1 (—)
RZQG71L
RZAG100M 3 (2.31) 2 (1.30)
RZQG100L
RZAG125M 4 (3.33) 3 (2.32) 2 (2.05)
RZQG125L
RZAG140M 4 (3.33) 3 (2.32) 2 (2.05)
RZQG140L
RZASG71M 2 (1.10) 1 (1.22)
RZQSG71L
RZASG100M 2 (1.65) 2 (—)
RZQSG100L
RZASG125M 4 (3.33) 3 (2.32) 2 (2.05)
RZQSG125L
RZASG140M 4 (3.33) 3 (2.32) 2 (2.05)
RZQSG140L
Combination FBA100A FBA125A FBA140A
RZAG71M
RZQG71L
RZAG100M 1 (0.73)
RZQG100L
RZAG125M 1 (0.74)
RZQG125L
RZAG140M 1 (0.74)
RZQG140L
RZASG71M
RZQSG71L
RZASG100M 1 (—)
RZQSG100L
RZASG125M 1 (0.74)
RZQSG125L
RZASG140M 1 (0.74)
RZQSG140L
INFORMATION
In case of group control it is not necessary to address the
indoor unit. The address is automatically set when the
power is activated.
6 Configuration
6.1 Field settings
Make the following field settings so that they correspond with the
actual installation setup and with the needs of the user:
External static pressure setting using:
Airflow automatic adjustment setting
User interface
Time to clean air filter
To set airflow automatic adjustment
When the air conditioning unit is running in fan operation mode:
1 Stop the air conditioning unit.
2 Set second code number to 03.
Setting content: Then
2
M C1 C2
Airflow adjustment is OFF 11(21) 7 01
Press ON/OFF to return to normal operating
mode.
Possible consequence: The operation lamp
will light up and the unit will start the fan
operation for airflow automatic adjustment.
03
Operation stops after 1 to 8 minutes.
Possible consequence: Setting is finished
and the operation lamp will be off.
02
If there is no change after airflow adjustment, perform the setting
again.
User interface
Check the indoor unit setting: the second code number of mode
11(21) must be set to 01.
(2)
Field settings are defined as follows:
M: Mode number – First number: for group of units – Number between brackets: for individual unit
C1: First code number
C2: Second code number
: Default