Engineering & Physical Data
Safety Device
MODEL
INDOOR FFN10/15CV1 FCN20/25/30FV1
OUTDOOR RN10/15FV1 RN28/30CV1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE N/A N/A
OPEN kPa / psi N/A N/A
CLOSE kPa / psi N/A N/A
LOW PRESSURE
SWITCH
TYPE N/A N/A
OPEN kPa / psi N/A N/A
CLOSE kPa / psi N/A N/A
PHASE SEQUENCER N/A
DISC. THERMOSTAT SETTING °C / F N/A
MODEL
INDOOR FCN35FV1 FCN40FV1
OUTDOOR RN35DV1 RN40DY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE NC NC
OPEN kPa / psi 4140 / 600 4140 / 600
CLOSE kPa / psi 3310 / 480 3310 / 480
LOW PRESSURE
SWITCH
TYPE NC NC
OPEN kPa / psi 48 / 7 48 / 7
CLOSE kPa / psi 152 / 22 152 / 22
PHASE SEQUENCER N/A YES
DISC. THERMOSTAT SETTING °C / F N/A 125 / 257
MODEL
INDOOR FCN50FV1
OUTDOOR RN50DY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 4140 / 600
CLOSE kPa / psi 3310 / 480
LOW PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 48 / 7
CLOSE kPa / psi 152 / 22
PHASE SEQUENCER YES
DISC. THERMOSTAT SETTING °C / F 125 / 257
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.