15
Sound Data
Sound Data
Sound Pressure Level
Model Speed
1/1 Octave Sound Pressure (dB, ref 20μPa)
Overall
(dBA)
Noise
Criteria
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
FFN10CV1
High 42 45 40 35 27 20 10 41 35
Med 40 42 37 32 24 15 7 38 32
Low 38 40 34 28 20 10 5 35 29
FFN15CV1
High 45 45 40 35 27 20 11 41 35
Med 41 42 37 32 23 15 9 38 32
Low 38 38 33 28 18 9 8 34 28
FCN20FV1
High 43 39 38 31 25 18 8 38 33
Med 42 37 34 28 22 14 7 35 29
Low 42 35 31 26 20 14 7 33 25
Quiet 41 28 25 22 17 12 5 29 21
FCN25FV1
High 42 39 39 32 28 22 9 39 34
Med 40 38 37 30 25 17 7 37 32
Low 38 36 34 26 21 13 6 34 29
Quiet 35 32 30 25 20 12 5 31 24
FCN30FV1
High 43 41 40 35 32 25 14 41 35
Med 41 40 37 31 28 19 11 38 32
Low 40 37 34 28 24 16 11 35 29
Quiet 38 34 30 26 21 15 11 32 24
FCN35FV1
High 47 46 45 41 35 30 21 46 40
Med 47 41 40 35 30 25 18 41 35
Low 46 37 35 31 24 22 17 37 30
Quiet 44 34 32 26 22 21 17 34 26
FCN40FV1
High 51 48 46 43 38 34 22 48 42
Med 51 45 43 40 34 29 18 45 39
Low 51 41 39 34 29 24 15 41 34
Quiet 49 37 34 29 23 18 11 37 31
FCN50FV1
High 51 48 46 43 38 34 22 48 42
Med 51 45 43 40 34 29 18 45 39
Low 51 41 39 34 29 24 15 41 34
Quiet 49 37 34 29 23 18 11 37 31
Model Measuring Location
FFN10CV1
FFN15CV1
FCN20FV1
FCN25FV1
Microphone
1.4m
Standard : JIS C 9612
FCN30FV1
FCN35FV1
FCN40FV1
FCN50FV1
Microphone
1.5m
Standard: JIS B 8616