Error Codes ESIE05-04
3–34 Part 3 – Troubleshooting
Troubleshooting
Remark If "A3" is detected by a PC board which is not mounted with X15A, the PC board is defective.
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Begin
Istheunita
cassetteorbuilt-in
type?
Isa
drainpump
connectedtothe
indoorunit
PCB?
Does
thedrainpump
workafterrestarting
operation?
Isthe
drainwater
levelabnormally
high?
Isthe
floatswitch
connectedto
X15A?
Does"A3"
appearontheremote
controllerdisplay?
220-240
VAC?
Isthere
continuity?
Isthe
optionaldrain
raisingmechanism
connected?
Istheshort-
circuitconnector
connectedtoX15Aonthe
indoorunit
PCB?
Connectthe
Short-circuit
connector.
Replacethe
Short-circuit
connector
Setto
"emergency"and
checkthevoltage
ofX25A.
Replacethe
drainpump.
Removethefloatswitchfrom
X15A,short-circuitX15A,and
restartoperation.
Replaceindoor
unitPCB.
Thereisamalfunction
ofthedrainsystem.
Replacefloat
switch.
Replacethe
indoorunitPCB.
Connect
floatswitch
Connectthe
drainpump.
Replaceindoor
unitPCB.
Checkthecontinuityofthe
short-circuitconnector.
No
Yes
Yes
Yes
Yes Yes
Yes
Yes
Yes
Yes
No No
Yes
No
No
No
No No
No
No
Yes