ESIE05-04 Field Settings
Part 4 Commissioning and Test Run 4–15
3
4
5
1
2.6 Setting the Ceiling Height
Incorrectly setting If you set the controller incorrectly, a connection mistake malfunction “UA” will appear on the remote
controller display.
See ’Malfunctioning Field Setting Switch (UA)’ on page 3–50.
Mode No. 13 or 23
First code No. 0
Set the second code No., according to the tables below.
FHQ
FAQ
FCQ and FUQ
Second code No. Ceiling-suspended type
01 Height < 2.7 m
02 2.7 m < height < 3.5 m
03 Not used
Second code No. Wall-mounted type
01 Normal
02 High
03 Extra high
Indoor unit Second code No. 4-way outlet 3-way outlet 2-way outlet
FCQ35-71 01 < 2.7 m < 3.0 m < 3.5 m
02 < 3.0 m < 3.3 m < 3.8 m
03 < 3.5 m < 3.5 m
FCQ100-125-140 01 < 3.2 m < 3.6 m < 4.2 m
02 < 3.6 m < 4.0 m < 4.2 m
03 < 4.2 m < 4.2 m
FUQ 01 < 2.7 m < 3.0 m < 3.5 m
02 < 3.0 m < 3.5 m < 3.8 m
03 < 3.5 m < 3.8 m