ESIE05-04 Disassembly and Maintenance
Part 5 – Disassembly and Maintenance 5–119
3
5
1
5
1.15.6 Removal of Fan Motor and Fan Rotor
Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step Procedure Points
Q Removing the front grille in
accordance with "Removal
of Front Grille".
Removing the electrical box
in accordance with
"Removal of Electrical Box".
1 Removing the fan motor
1 Insert a Phillips tip
screwdriver into the air
outlet and remove the
screws fixing the fan
motor and fan rotor. (The
screws can be removed
without removing of
horizontal blade.)
2 Remove the two screws
on the bearing cover (1)
and (2) and dismantle the
covers.
3 Take out the fan motor
sideways.
2 Removing the fan rotor
Q Removing the heat
exchanger in accordance
with "Removal of Heat
Exchanger".
1 Remove the two screws
to dismantle the rotor
cover.
2 Pull the fan rotor out.