2 | Components
Service manual
134
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
A RXA42~50A unit
a Reactor L803
b Reactor L804
A RXA42~50B unit
a Reactor L803
b Reactor L804
2 Remove the main PCB, see "Repair procedures" [4 108]. The reactor
measuring points are ONLY reachable on the back side of the main PCB.
3 Measure the resistance of the reactor using a low ohm multi meter.
Result: The resistance MUST be as follows:
Measuring points Resistance
c‑d 15~25mΩ
e 152~228mΩ