2 | Components
Service manual
136
FTXA20~50A(W)(S)(T) + FTXA20~50B(B)(S)(T) + RXA42+50A +
RXA20~35A(9) + RXA42+50B
Split Stylish R32
ESIE18-03D – 2021.05
A RXA42~50A unit
a L803
b L804
c Measuring point
d Measuring point
A RXA42~50B unit
a L803
b L804
c Measuring point
d Measuring point
Is the inductance measurement
correct?
Action
Yes Return to the troubleshooting of the
specific error and continue with the
next step.
No Replace the reactor, see "2.15.2Repair
procedures"[4136].
2.15.2 Repair procedures
As the reactors are part of the main PCB, replace the complete main PCB. See
"2.12Main PCB"[491].