3 | Troubleshooting
Service manual
18
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32
ESIE22-04 – 2022.04
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.5.6 C9-00 – Room thermistor abnormality
Trigger Effect Reset
Resistance value is out of
range. Temperature
measured <–43.6°C or
>90°C.
Unit will stop operating. Automatic reset when
resistance is within range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the indoor unit air (room) thermistor. See Thermistors.
Possible cause: Faulty indoor unit air (room) thermistor.
2 Perform a check of the indoor unit main PCB. See Indoor unit PCB.
Possible cause: Faulty indoor unit main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.5.7 CC-00 – Humidity sensor abnormality
Trigger Effect Reset
Disconnected sensor
Broken sensor
Communication error
Unit will stop operating. Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the humidity sensor. See Humidity sensor.
Possible cause: Faulty humidity sensor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.