EasyManuals Logo

Daikin FWF04C User Manual

Daikin FWF04C
143 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
7
Application Information
Application Information
Model: FWW
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature
19.0 / 66.2 14.0 / 57.2
Maximum indoor
temperature
32.0 / 89.6 23.0 / 73.4
Heating Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature
15.0 / 59.0 -
Maximum indoor
temperature
27.0 / 80.6 -
Ts: Dry bulb temperature. Th: Wet bulb temperature.
Model: FWF
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (2 Pipes) (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature
19.0 / 66.2 14.0 / 57.2
Maximum indoor
temperature
32.0 / 89.6 23.0 / 73.4
Heating Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature
15.0 / 59.0 -
Maximum indoor
temperature
27.0 / 80.6 -
Ts: Dry bulb temperature. Th: Wet bulb temperature.
Model: FWK & FWKE
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (2 Pipes) (Heating), 35°C ~ 70°C (4 Pipes) (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature
16.0 / 60.8 11.0 / 51.8
Maximum indoor
temperature
32.0 / 89.6 23.0 / 73.4
Heating Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature
16.0 / 60.8 -
Maximum indoor
temperature
30.0 / 86.0 -
Ts: Dry bulb temperature. Th: Wet bulb temperature.
Model: FWE
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature
19.0 / 66.2 14.0 / 57.2
Maximum indoor
temperature
32.0 / 89.6 23.0 / 73.4
Heating Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature
15.0 / 59.0 -
Maximum indoor
temperature
27.0 / 80.6 -
Ts: Dry bulb temperature. Th: Wet bulb temperature.