Installation EDUS39-600-F6
38 FXAQ-M
(3) How to select FORCED OFF and ON/OFF OPERATION
Turn the power on and then use the remote controller to
select operation.
Set the remote controller to the field set mode. For details,
refer to the “HOW TO SET IN THE FIELD”, in the remote
controller manual.
When in the field set mode, select mode No. 12, then set
the first code (switch) No. to “1”. Then set second code
(position) No. to “01” for FORCED OFF and “02” for ON/
OFF OPERATION.
(FORCED OFF at factory set) (Refer to Fig. 31)
8-5 CENTRALIZED CONTROL
For centralized control, it is necessary to designate the group No. For details, refer to the manual of each optional
controllers for centralized control.
9. FIELD SETTINGS
(1) Make sure the service lids are closed on the indoor and outdoor units.
(2) Field settings must be made from the remote controller in accordance with installation conditions.
Settings can be made by changing the “Mode No”, “FIRST CODE NO.” and “SECOND CODE NO.”.
Refer to the installation manual attached to the remote controller.
The “Field Settings” included with the remote controller lists the order of the settings and method of operation.
*Setting is made in all units in a group. To set for individual indoor units or to check the setting, use the mode Nos.
(with “2” in upper digit) in parentheses ( ).
9-1 SETTING AIR FILTER SIGN
Remote controllers are equipped with liquid crystal display air filter signs to display the time to clean air filters.
Change the SECOND CODE NO. according to Table 3 depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to “01” for air filter contamination-light)
Table 3
9-2 SETTING AIR FLOWRATE INCREASE MODE
It is possible to raise set air flow (HIGH and LOW) from the field. Change the SECOND CODE NO. as shown in Table
4 to suit your needs.
SECOND CODE NO. is factory set to [01] for Standard.
Table 4
When using wireless remote controllers, an address setting is necessary. Refer to the installation manual
attached to the wireless remote controller for setting instructions.
Input OFF enables control by remote controller. Input ON OFF turns OFF unit.
Setting Elapsed time till display signals
when to clean air filter
Mode No. FIRST CODE NO. SECOND CODE NO.
Air filter
contamination-light
Approx. 200 hrs.
10 (20) 0
01
Air filter
contamination-heavy
Approx. 100 hrs. 02
Setting Mode No. FIRST CODE NO. SECOND CODE NO.
Standard
13 (23) 0
01
A little increase 02
Increase 03
SETTING
Mode No.
SECOND CODE NO.
FIELD SET MODE
Fig. 31
FIRST CODE NO.