English 23
Wiring Method (See ‘‘ELECTRIC WIRING WORK’’)
(3) Remove the control box lid
(4) Add remote control 2 (slave) to the terminal block for remote controller (P1, P2) in the control box.
(There is no polarity.) (Refer to Fig. 30 and 8-3.)
9-4 Computerised control (forced off and on/off operation)
(1) Wire specifications and how to perform wiring
• Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller.
(2) Actuation
• The following table explains FORCED OFF and ON/OFF OPERATIONS in response to Input A.
(3) How to select FORCED OFF and ON/OFF OPERATION
• Turn the power on and then use the remote controller to select operation.
9-5 Centralized control
• For centralized control, it is necessary to designate the group No. For details, refer to the manual of each
optional controllers for centralized control.
Wire specificationCONDUCTORSTRANDEDNONSHIELDEDCOPPERCABLE06#ORVINYLJACKET
Gauge AWG18
Length Max. ft.
External terminal Contact that can ensure the minimum applicable load of 15 V DC, 1 mA.
FORCED OFF ON/OFF OPERATION
Input “ON” stops operation (impossible by remote controllers.) Input OFF → ON turns ON unit.
Input OFF enables control by remote controller. Input ON → OFF turns OFF unit.
S
M
S
S
M
Remote
controller
PC board
(Factory setting)
Fig. 33
Only one remote controller needs
to be changed if factory settings
have remained untoUched.
F2 T1 T2
FORCED
OFF
Input A