Indoor Units • Round Flow Cassette • FXFQ-PVE9
1 Specifications
1-2 ELECTRICAL SPECIFICATIONS (50HZ)
FXFQ25PVE9 FXFQ32PVE9 FXFQ40PVE9 FXFQ50PVE9 FXFQ63PVE9 FXFQ80PVE9
FXFQ100PVE9 FXFQ125PVE9
Power Supply Name VE
Phase 1~
Frequency Hz 50
Voltage V 220-240
Current Minimum circuit amps (MCA) A 0.3 0.3 0.3 0.3 0.4 0.5 1.3 1.5
Maximum fuse amps (MFA) A 15 15 15 15 15 15 15 15
Full load amps (FLA) A 0.2 0.2 0.2 0.2 0.3 0.4 1.0 1.2
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS (60HZ)
FXFQ25PVE9 FXFQ32PVE9 FXFQ40PVE9 FXFQ50PVE9 FXFQ63PVE9 FXFQ80PVE9
FXFQ100PVE9 FXFQ125PVE9
Power Supply Name VE
Phase 1~
Frequency Hz 60
Voltage V 220
Current Minimum circuit amps (MCA) A 0.3 0.3 0.3 0.3 0.4 0.5 1.3 1.5
Maximum fuse amps (MFA) A 15 15 15 15 15 15 15 15
Full load amps (FLA) A 0.2 0.2 0.2 0.2 0.3 0.4 1.0 1.2
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker