15 English
9. MOUNTING SUCTION GRILLE · DECO-
RATION SIDE PANEL
Install securely in the reverse order when decoration side panel
and suction grille were removed.
• When installing the suction grille, hang the string of the suc-
tion grille to the hanging part of the indoor unit shown Fig. 35.
When closing the suction grille, the strap may get caught.
Confirm that the strap does not stick out of the side of the
suction grille before closing.
10. FIELD SETTING AND TEST OPERATION
<<Refer to also the installation manual attached to the out-
door unit.>>
Before carrying out field setting, check the items mentioned
in the clause 2 “1. Items to be checked after the installa-
tion work is completed” on page 3.
• Check if all the installation and piping works for the air
conditioner are completed.
• Check if the control box lids of the air conditioner are
closed.
<FIELD SETTING>
<After turn on the power supply, carry out field setting from
the remote controller according to the installation state.>
• Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.”
and “SECOND CODE No.”.
The settings shown by “ ” in the table indicate those
when shipped from the factory.
• The method of setting procedure and operation is shown in
the installation manual attached to the remote controller.
(Note) Though setting of “Mode No.” is carried out as a
group, if you intend to carry out individual setting by
each indoor unit or confirmation after setting, carry
out setting with the “Mode No.” shown in the
parenthesis ( ).
• In case of remote control, for changeover of input to
FORCED OFF or to ON/OFF OPERATION.
[1] Enter into the field setting mode with the remote controller.
[2] Select Mode No. “12”.
[3] Set the FIRST CODE No. to “1”.
[4-1] For FORCE OFF, set the SECOND CODE No. to “01”.
[4-2] For ON/OFF OPERATION, set the SECOND CODE
No. to “02”.
(It is set to FORCED OFF when shipped from the factory.)
• Ask your customer to keep the manual attached to the
remote controller together with the operation manual.
• Do not carry out setting other than those shown in the table.
10-1 SETTING OF CEILING HEIGHT
• Set the SECOND CODE No. according to the ceiling height
as shown in the Table 3.
(The SECOND CODE No. is set at “01”, when shipping from
the factory.)
Table 3
Do not set the SECOND CODE No. “03”.
10-2 SETTING WHEN AN OPTIONAL ACCESSORY
IS ATTACHED
• For setting when attaching an optional accessory, refer to the
installation manual attached to the optional accessory.
10-3 WHEN USING WIRELESS REMOTE CONTROL-
LER
• When using a wireless remote controller, it is necessary to
set the wireless remote controller address. Refer to the
installation manual attached to the wireless remote control-
ler.
10-4 SETTING FAN SPEED DURING THERMOSTAT
OFF
• Set the fan speed according to the using environment after
consultation with your customer.
(When shipping, the SECOND CODE No. “02” is set for the
fan speed during the cooler thermostat OFF, and other are
set at “01”.)
Table 4
10-5 SETTING FILTER SIGN
• A message to inform the air filter cleaning time will be indi-
cated on the remote controller.
• Set the SECOND CODE No. to the number shown in the
Table 5 according to the amount of dust or pollution in the
room.
• Though the indoor unit is equipped with the long life filter, it is
necessary to periodically clean the filter to avoid clogging of
the filter. Please also explain the set time to the customer.
• The periodical filter cleaning time can be shortened depend-
ing on the environment.
Strap
Strap
Round hole
Round hole
Hook
Hook
Cross hole
Indoor unit
Suction grille
Fig. 35
Ceiling height (m)
Mode No.
FIRST
CODE No.
SECOND
CODE No.
Type 32 Type 63 Type 100
Standard
2.7 or
less
2.7 or
less
3.8 or
less
13 (23) 0
01
High
ceiling
2.7-3.5 2.7-3.5 3.8-4.3 02
Setting
Mode
No.
FIRST
CODE No.
SECOND
CODE No.
Fan operates/stops
during thermostat
OFF (Cooling ·
heating)
Operates
11 (21) 2
01
Stops 02
Fan speed during
cooling thermostat
OFF
LL (Extra
low)
12 (22) 6
01
Setting 02
Fan speed during
heating thermostat
OFF
LL (Extra
low)
12 (22) 3
01
Setting 02
01_EN_3P368557-2D.fm Page 15 Wednesday, February 13, 2019 2:46 PM