Indoor Units • CONCEALED CEILING UNIT • FXMQ-PVE
1 Specifications
1-2 ELECTRICAL SPECIFICATIONS FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE
Power Supply Name VE
Phase 1~
Frequency Hz 50/60
Voltage V 220-240/220
Current Minimum circuit amps
(MCA)
A 1.4 1.6 1.8 2.3 2.9 3.4
Maximum fuse amps (MFA) A 16 16 16 16 16 16
Full load amps (FLA) A 1.1 1.3 1.4 1.8 2.3 2.7
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 16A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker