18 ED 15121
Holding Register
(4xxxx)
Fault Alarms Description
#1
647
COMPRESSOR SHUTDOWN - Oil Feed Pressure Sensor Fault Circuit #3, Comp
#1
0=Normal, 1=Alarm
648
COMPRESSOR SHUTDOWN - Oil Feed Pressure Sensor Fault Circuit #4, Comp
#1
0=Normal, 1=Alarm
661 SHUTDOWN – Phase Voltage Protection 0=Normal, 1=Alarm
662 COMPRESSOR SHUTDOWN - Starter Fault Compressor Circuit #1, Comp #1 0=Normal, 1=Alarm
664 COMPRESSOR SHUTDOWN - Starter Fault Compressor Circuit #2, Comp #1 0=Normal, 1=Alarm
666 COMPRESSOR SHUTDOWN - Starter Fault Compressor Circuit #3, Comp #1 0=Normal, 1=Alarm
667 COMPRESSOR SHUTDOWN - Starter Fault Compressor Circuit #4, Comp #1 0=Normal, 1=Alarm
698
COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault Circuit #1,
Comp #1
0=Normal, 1=Alarm
700
COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault Circuit #2,
Comp #1
0=Normal, 1=Alarm
702
COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault Circuit #3,
Comp #1
0=Normal, 1=Alarm
703
COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault Circuit #4,
Comp #1
0=Normal, 1=Alarm
723 Controller board offline Circuit #1 (Circuit number describes Control board number) 0=Normal, 1=Alarm
724 Controller board offline Circuit #2 (Circuit number describes Control board number) 0=Normal, 1=Alarm
725 Controller board offline Circuit #3 (Circuit number describes Control board number) 0=Normal, 1=Alarm
726 Controller board offline Circuit #4 (Circuit number describes Control board number) 0=Normal, 1=Alarm
755 Evaporator Entering Water Temperature Sensor Failure 0=Normal, 1=Alarm
756 COMPRESSOR SHUTDOWN - Slide position sensor fault Circuit #1, Comp#1 0=Normal, 1=Alarm
758 COMPRESSOR SHUTDOWN - Slide position sensor fault Circuit #2, Comp#1 0=Normal, 1=Alarm
760 COMPRESSOR SHUTDOWN - Slide position sensor fault Circuit #3, Comp#1 0=Normal, 1=Alarm
761 COMPRESSOR SHUTDOWN - Slide position sensor fault Circuit #4, Comp#1 0=Normal, 1=Alarm