18 ED 15121
Holding Register
(4xxxx)
Fault Alarms Description
#1
647
COMPRESSOR SHUTDOWN - Oil Feed Pressure Sensor Fault Circuit #3, Comp
#1
0=Normal, 1=Alarm
648
COMPRESSOR SHUTDOWN - Oil Feed Pressure Sensor Fault Circuit #4, Comp
#1
0=Normal, 1=Alarm
661 SHUTDOWN – Phase Voltage Protection 0=Normal, 1=Alarm
662 COMPRESSOR SHUTDOWN - Starter Fault Compressor Circuit #1, Comp #1 0=Normal, 1=Alarm
664 COMPRESSOR SHUTDOWN - Starter Fault Compressor Circuit #2, Comp #1 0=Normal, 1=Alarm
666 COMPRESSOR SHUTDOWN - Starter Fault Compressor Circuit #3, Comp #1 0=Normal, 1=Alarm
667 COMPRESSOR SHUTDOWN - Starter Fault Compressor Circuit #4, Comp #1 0=Normal, 1=Alarm
698
COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault Circuit #1,
Comp #1
0=Normal, 1=Alarm
700
COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault Circuit #2,
Comp #1
0=Normal, 1=Alarm
702
COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault Circuit #3,
Comp #1
0=Normal, 1=Alarm
703
COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault Circuit #4,
Comp #1
0=Normal, 1=Alarm
723 Controller board offline Circuit #1 (Circuit number describes Control board number) 0=Normal, 1=Alarm
724 Controller board offline Circuit #2 (Circuit number describes Control board number) 0=Normal, 1=Alarm
725 Controller board offline Circuit #3 (Circuit number describes Control board number) 0=Normal, 1=Alarm
726 Controller board offline Circuit #4 (Circuit number describes Control board number) 0=Normal, 1=Alarm
755 Evaporator Entering Water Temperature Sensor Failure 0=Normal, 1=Alarm
756 COMPRESSOR SHUTDOWN - Slide position sensor fault Circuit #1, Comp#1 0=Normal, 1=Alarm
758 COMPRESSOR SHUTDOWN - Slide position sensor fault Circuit #2, Comp#1 0=Normal, 1=Alarm
760 COMPRESSOR SHUTDOWN - Slide position sensor fault Circuit #3, Comp#1 0=Normal, 1=Alarm
761 COMPRESSOR SHUTDOWN - Slide position sensor fault Circuit #4, Comp#1 0=Normal, 1=Alarm

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin McQuay MicroTech III and is the answer not in the manual?

Daikin McQuay MicroTech III Specifications

General IconGeneral
BrandDaikin
ModelMcQuay MicroTech III
CategoryChiller
LanguageEnglish

Related product manuals