10.8.2 Low Pressure Start Fail
This alarm indicates that at the compressor start the evaporating pressure or condensing pressure is below a minimum
fixed limit at compressor start.
Symptom
Solution
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s
display.
String in the alarm list:
Cx OffStartFailEvpPrLo
String in the alarm log:
Cx OffStartFailEvpPrLo
String in the alarm snapshot
Cx OffStartFailEvpPrLo
Check the operating envelope for this
machine.
Check refrigerant charge.
Check for gas leakage with a sniffer.
Reset
Notes
Local HMI
Network
Auto