10.10.2 High Condenser Pressure Hold/Unload
These events are generated to indicate a temporary condition with the condensing pressure above the hold and unload
limits.
Symptom
Circuit status is
Run: High Cond Press
The compressor does not load
anymore or even unload.
String in the Event log:
CxCmp1 HiCondPrHold
CxCmp1 HiCondPrUnld