3 | Components
Service manual
175
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
Pins Measured resistance (Ω)
2-3 706.8~813.2
2-4
2-5
3-4
3-5
4-5
Swing flap motor resistance
measurements are correct?
Action
Yes Replace the swing flap motor wiring
harness, see "Repair
procedures"[4175].
No Replace the swing flap motor, see
"Repair procedures"[4175].
Repair procedures
To remove the swing flap motor
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see "3.14Plate work"[4151].
1 Remove the switch box, see "3.14Plate work"[4151].
2 Remove the main swing flap from the indoor unit (by clicking it out).
3 Remove the secondary swing flap from the indoor unit (by clicking it out).
4 Remove the screw from the swing flap motor.
b
a
c d
a Main swing flap
b Secondary swing flap
c Screw (swing flap motor fixation)
d Swing flap motor
5 Remove (pull back) the swing flap motor from the indoor unit.
6 Disconnect the wiring harness from the swing flap motor.
7 To install the swing flap motor, see "Repair procedures"[4175].