EasyManuals Logo

Daikin Perfera ATXM50R User Manual

Daikin Perfera ATXM50R
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #251 background imageLoading...
Page #251 background image
6 | Technical data
Service manual
251
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
6.7 Field settings
6.7.1 To control heating only mode
Prerequisite: Stop operation of the unit.
1 Press
, , and simultaneously.
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 19.
7 Press
to confirm.
8 Press
.
9 Select 1 (0: factory setting, 1: heating only).
10 Press
to confirm.
6.7.2 To adjust target set temperature in heating operation
INFORMATION
When there is a big difference between the indoor room temperature and the set
temperature in heating mode, adjust the target set temperature field setting.
Target temperature = remote controller set temperature + 2.5°C. For
example:
Remote controller set temperature = 20°C
Target temperature = 20°C + 2.5°C = 22.5°C
Thermo off temperature = 24.5°C
1 Press
, , and simultaneously.
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 7.
7 Press
to confirm.
8 Press
.
9 Select the value to set the desired target temperature:
0 = –2,0°C
1 = –1,0°C
2 = 0°C (factory setting)
3 = +1,0°C
4 = +2,0°C
10 Press
to confirm.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Perfera ATXM50R and is the answer not in the manual?

Daikin Perfera ATXM50R Specifications

General IconGeneral
BrandDaikin
ModelPerfera ATXM50R
CategoryAir Conditioner
LanguageEnglish

Related product manuals