8 | Electrical installation
Installer reference guide
42
CVXM20A + FVXM25~50A
Split system air conditioners
4P625991-1C – 2021.09
Wire type Installation method
Single-core wire
c b
c
aa
A
AA´
a Curled single-core wire
b Screw
c Flat washer
Stranded conductor wire
with round crimp-style
terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
1-3
8.1.3 Specifications of standard wiring components
Component
Interconnection cable (indoor↔outdoor) 4-core cable 1.5mm²~2.5mm²
andapplicable for 220~240V
H05RN-F (60245 IEC 57)
8.2 To connect the electrical wiring to the indoor unit
1 Open the terminal block. See "6.2Opening the indoor unit"[424].
2 Strip the wire ends approximately 15mm.
3 Match wire colours with terminal numbers on indoor and outdoor unit’s
terminal blocks and firmly screw wires to the corresponding terminals.
4 Connect the earth wires to the corresponding terminals.