EasyManuals Logo

Daikin RCS Series User Manual

Daikin RCS Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
Charging Charts
Figure 17: 6-1/2 Ton Charging Charts
115
105
95
85
75
65
55
175
200
225
250
275
300
325
350
375
400
425
450
475
500
100.0 105.0 110.0 115.0 120.0 125.0 130.0 135.0 140.0 145.0 150.0 155.0 160.0 165.0
A/C SYSTEM CHARGE CHART
CAUTION: RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS BEFORE FINAL REFRIGERANT CHECK!
INSTRUCTIONS: 1. MEASURE PRESSURE AT COMPRESSOR SUCTION AND LIQUID.
2. MEASURE OUTDOOR AMBIENT TO UNIT.
3. PLACE AN “X” ON THE CHART WHERE THE SUCTION AND LIQUID INTERSECT.
4. IF “X” IS BELOW OUTDOOR AMBIENT TEMPERATURE LINE, ADD CHARGE AND REPEAT STEPS 1-3.
5. IF “X” IS ABOVE AMBIENT TEMPERATURE LINE, RECOVER EXCESS CHARGE AND REPEAT STEPS 1-3.
92-102644-17-00
Vapor Pressure (PSIG)
Pressure at Liquid Service Port (PSIG)
Outdoor Ambient (°F DB)

www.DaikinApplied.com 21 IM 962-4 • AIR-COOLED SPLIT SYSTEM CONDENSERS