SiUS181631EA Troubleshooting for FFQ Series
Troubleshooting 209
5.3 Indoor Fan Motor (DC Motor) or Related Abnormality
Error Code
A6
Method of Error
Detection
The rotation speed detected by the Hall IC during fan motor operation determines abnormal fan
motor operation.
Error Decision
Conditions
The fan motor is not revved up.
Supposed
Causes
îš„
Layer short inside the fan motor winding
îš„
Breaking of wire inside the fan motor
îš„
Breaking of the fan motor lead wires
îš„
Defective indoor unit PCB