SiUS281811EA Check
Part 6 Service Diagnosis 309
FHQ-P, FHQ-M
RZR18/24TAVJU
RZQ18/24TAVJU
3
Orange
White
1
Yellow
2
Red
5
6
Brown
4
Blue
Measuring points Judgment criteria
1 - 3 300 Ω
1 - 5 150 Ω
2 - 4 300 Ω
2 - 6 150 Ω
(White) 1
(Yellow) 2
(Orange) 3
(Blue) 4
— 5
(Red) 6
X21A (Y1E)
Measuring points Judgment criteria
1 - 6
35-55 Ω
2 - 6
3 - 6
4 - 6