Check SiUS281811EA
308 Part 6 Service Diagnosis
5.14 Electronic Expansion Valve Coil Check
CHECK 18 Measure the connector pin-to-pin resistance and make sure that the resistance value is within the
range listed in the table below.
FCQ-TA, FTQ-TA
FBQ-P, FAQ-TA
Orange 1
Red 2
Yellow 3
Black 4
— 5
Gray 6
Measuring points Judgment criteria
1 - 6
35-55 Ω
2 - 6
3 - 6
4 - 6
White 1
Yellow 2
Orange 3
Blue 4
Red 5
Brown 6
Measuring points Judgment criteria
1 - 3 300 Ω
1 - 5 150 Ω
2 - 4 300 Ω
2 - 6 150 Ω