EDUS281120_a Airflow Auto Adjustment Characteristics
RZR-P, RZQ-P(9) 95
11.Airflow Auto Adjustment Characteristics
FBQ18PVJU
FBQ24PVJU
3D066130B
Notes:
1. The auto airflow adjustment function can
be used to offset a reduction in airflow.
This function must be performed during
installation and commissioning and will adjust
the airflow to within ± 10% of the rated value.
2. After completing the installation of the indoor
unit ductwork, use the remote controller
to set the airflow auto-adjustment.
3. For instructions on how to set the Airflow Auto-
Adjustment, refer to the Installation Manual
attached to the indoor unit.
4. External static pressure of 0.2 to 0.8Wg can be
adjusted by the Airflow Auto-Adjustment fu
nction
if airflow is HH.
5. If the Auto-Adjustment function is not utilized, the
airflow rate will be in accordance with the fan
characteristics shown above.
6. This figure shows a fan’s characteristics at the
time of HH and H and L.
7. The remote controller can be used to change
HH, H, and L.
8. ESP: external static pressure.
9. Set the external static pressure of the suction
duct at 0.6” Wg or less.
3D066131B
Notes:
1. The auto airflow adjustment function can
be used to offset a reduction in airflow.
This function must be performed during
installation and commissioning and will adjust
the airflow to within ± 10% of the rated value.
2. After completing the installation of the indoor
unit ductwork, use the remote controller
to set the airflow auto-adjustment.
3. For instructions on how to set the Airflow Auto-
Adjustment, refer to the Installation Manual
attached to the indoor unit.
4. External static pressure of 0.2 to 0.8Wg can be
adjusted by the Airflow Auto-Adjustment fu
nction
if airflow is HH.
5. If the Auto-Adjustment function is not utilized, the
airflow rate will be in accordance with the fan
characteristics shown above.
6. This figure shows a fan’s characteristics at the
time of HH and H and L.
7. The remote controller can be used to change
HH, H, and L.
8. ESP: external static pressure.
9. Set the external static pressure of the suction
duct at 0.6” Wg or less.