EasyManua.ls Logo

Daikin SkyAir FHQ24PVJU - Page 97

Daikin SkyAir FHQ24PVJU
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Airflow Auto Adjustment Characteristics EDUS281120_a
96 RZR-P, RZQ-P(9)
FBQ30PVJU
FBQ36PVJU
3D066132B
Notes:
1. The auto airflow adjustment function can
be used to offset a reduction in airflow.
This function must be performed during
installation and commissioning and will adjust
the airflow to within ± 10% of the rated value.
2. After completing the installation of the indoor
unit ductwork, use the remote controller
to set the airflow auto-adjustment.
3. For instructions on how to set the Airflow Auto-
Adjustment, refer to the Installation Manual
attached to the indoor unit.
4. External static pressure of 0.2 to 0.8Wg can be
adjusted by the Airflow Auto-Adjustment fu
nction
if airflow is HH.
5. If the Auto-Adjustment function is not utilized, the
airflow rate will be in accordance with the fan
characteristics shown above.
6. This figure shows a fan’s characteristics at the
time of HH and H and L.
7. The remote controller can be used to change
HH, H, and L.
8. ESP: external static pressure.
9. Set the external static pressure of the suction
duct at 0.6” Wg or less.
3D066133
Notes:
1. The auto airflow adjustment function can
be used to offset a reduction in airflow.
This function must be performed during
installation and commissioning and will adjust
the airflow to within ± 10% of the rated value.
2. After completing the installation of the indoor
unit ductwork, use the remote controller
to set the airflow auto-adjustment.
3. For instructions on how to set the Airflow Auto-
Adjustment, refer to the Installation Manual
attached to the indoor unit.
4. External static pressure of 0.2 to 0.8Wg can be
adjusted by the Airflow Auto-Adjustment f
unction
if airflow is HH.
5. If the Auto-Adjustment function is not utilized, the
airflow rate will be in accordance with the fan
characteristics shown above.
6. This figure shows a fan’s characteristics at the
time of HH and H and L.
7. The remote controller can be used to change
HH, H, and L.
8. ESP: external static pressure.
9. Set the external static pressure of the suction
duct at 0.6” Wg or less.

Other manuals for Daikin SkyAir FHQ24PVJU

Related product manuals