Si71-502 Troubleshooting
Troubleshooting 43
1.8 Dedicated LCD Remote Controller
When
88
remains on remote controller display.
Error Detection
Method
When
88
remains on remote controller display.
Error Generating
Conditions
Possible Causes Master-slave setting of remote controller
Remote controller PCB assembly error
Main unit PCB assembly error
Troubleshooting
Dedicated Remote Controller
Main Unit PCB
Check to see if master-
slave remote controller is
used.
Check microcomputer
operation monitor on
main unit PCB.
Is it flashing?
YES
YES
Change master-slave selection
switch to set proper master-
slave relation.
One should be set to Master,
and the other set to Slave.
Replace remote controller.
Replace main unit PCB.
Is
master-slave
remote controller
used?
(HF007)
NO
NO
Master-slave
selection switch
Remote controller
PCB assembly
(HL030)
Exhaust
air fan
Supply
air fan
CN3 CN4CN2CN1
CN7
FuL 10A
CN13
CN8
CN12CN5 CN6CN9
KRP
50-2
CN11
CN10
LN
P2 P1 F1 F2 J1 J2 JC
LED A
(HL031)
(Microcomputor Operation Monitor)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VAM 350GJVE and is the answer not in the manual?

Daikin VAM 350GJVE Specifications

General IconGeneral
BrandDaikin
ModelVAM 350GJVE
CategoryFan
LanguageEnglish

Related product manuals