Penyelesaian Masalah Menggunakan Remote Kontrol
Penyelesaian Masalah
Perhatian
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Properly connect the connectors.
Replace it with a correct PCB.
Replace the INV. compressor.
Replace the fan motor.
Not the "LC" error. Check the
Kode kesalahan
again.
Replace the PCB Inverter (A4P).
Replace the unit outdoor main
PCB (A1P).
Continue the operation.
(It is supposed that the error
results from causes such as
instantaneous power failure.)
Catatan:
1. Disconnect the connector once, then reconnect it and check that it is securely connected.
Are the
connectors of
the unit outdoor main
PCB, and inverter PCB all
securely connected?
(1)
Is the type of the
inverter PCB correct?
The INV.
compressor has
insulation resistance of not
more than
100k.
NO
The fan
motor has insulation
resistance of not more
than 1M.
NO
The micro-
computer normal
monitor (green) of the unit
outdoor
main PCB (A1P) is
blinking.
YES
The micro-computer
normal monitor (green) of the
inverter PCB (A4P) is
blinking.
YES