English 12
H
eat Recovery series (RQ(C)EQ)
Example of connection
(Connection of 8 indoor units)
Indoor
unit
side
Outdoor
unit
side
1 2
BS
Unit
Suction gas pipe
HP/LP gas pipe
Liquid pipe
(Suction) gas pipe
Liquid pipe
Piping from outdoor unit to BS unit
Piping from BS unit to indoor unit or 
Piping from Refrigerant branch kit to
indoor unit used as cooling only
(Bold):3 pipes
(Thin):2 pipes
(*1) “ ” Indicate the Outdoor unit multi
connection piping kit.
(*2) In case of multi outdoor system, re-read
“outdoor unit” to “the first Outdoor unit
multi connection piping kit” as seen from
the indoor unit.
Branch with REFNET joint Branch with REFNET joint and header Branch with REFNET header
Multi
outdoor
system
(RQCEQ)
Maximum
allowable
length
Allowable
height
difference
Allowable length after the branch
Between outdoor unit (*2)
and indoor unit
Between first outdoor unit multi
connection piping kit and outdoor unit
(in case of multi system)
Between outdoor and indoor units
Between indoor and indoor units
Between outdoor and outdoor units
Actual pipe
length
Equivalent
length
Actual and
Equivalent
pipe length
Actual pipe
length
Difference in height
Difference in height
Difference in height
Total extension length
Pipe length between outdoor unit (*2) and indoor unit 120m
Example 8 : a + b + c + d + e + s 120m
Example 6 : a + b + 120m, 8 : a + m + n + p 120m
Example 8 : a + o
120m
Total piping length from outdoor unit (*2) to all indoor unit 300m
Actual pipe length from first outdoor unit multi connection piping kit to outdoor unit 10m
Equivalent pipe length from first outdoor unit multi connection piping kit to outdoor unit 13m
Actual pipe length from first refrigerant branch kit (either REFNET joint or REFNET header) to indoor unit 40m
Example 8 : b + c + d + e + s 40m
Difference in height between outdoor unit and indoor unit (H1) 50m (Max 40m if the outdoor unit is below)
Difference in height between adjacent indoor units (H2) 15m
Difference in height between adjacent outdoor units (H3) 5m
Outdoor unit
r
10m
(Equivalent length
13m)
u + s
10m
(Equivalent length
13m)
u + t
10m
(Equivalent length
13m)
Example 6 : b + 40m, 8: m + n + p 40m Example 8 : o
40m
B1 ~ B4
: BS Unit
1 ~ 6  :
Indoor unit (Cool/Heat selection possible)
7 , 8 : Indoor unit (Cooling only)
B1 ~ B5
: BS Unit
1 ~ 4 , 7 , 8 :
Indoor unit (Cool/Heat selection possible)
5 , 6 : Indoor unit (Cooling only)
B1 ~ B4
: BS Unit
1 ~ 6 : Indoor unit (Cool/Heat selection possible)
7 , 8 : Indoor unit (Cooling only)
r
t
s
u
1
2
Outdoor unit multi connection piping kit and
Refrigerant branch kit selection
Refrigerant branch kit must be used to
prescribed kit.
Use this table for kit selection.
How to select the REFNET joint How to select the REFNET header
When using REFNET joint at the first branch counted from the outdoor unit side,
choose from the following table in accordance with the outdoor unit capacity type.
(Example : REFNET joint A)
Choose from the following table in accordance with the total capacity index of all
the indoor units connected below the REFNET header.
250 type indoor unit can not be connected below the REFNET header.
How to select the outdoor unit multi connection piping kit
(This is required when the system is multi outdoor unit system.)
Choose from the following table in accordance with the number of outdoor units.
Choose the REFNET joints other than the first branch from the following table in accordance
with the total capacity index of all the indoor units connected below the REFNET joint.
Outdoor unit capacity type
Q280 type
Q360~712 type
Q744 type ~
Indoor unit total capacity index
x < 200
200 x < 290
290 x < 640
640 x
Refrigerant branch kit name
KHRP25A33T
KHRP25A72T+KHRP25M72TP
KHRP25A73T+KHRP25M73TP
3 pipes
KHRP25A22T
KHRP25A33T
KHRP25A72T+KHRP25M72TP
KHRP25A73T+KHRP25M73TP
2 pipes
KHRP26A22T
KHRP26A33T
KHRP26A72T
Refrigerant branch kit name
Indoor unit total capacity index
x < 200
200 x < 290
290 x < 640
640 x
Number of outdoor unit
2 units
3 units
4 units
Connecting piping kit name
BHFP26P36C
BHFP26P63C
BHFP26P84C
3 pipes
KHRP25M33H
KHRP25M72H+KHRP25M72HP
KHRP25M73H+KHRP25M73HP
2 pipes
KHRP26M22H or KHRP26M33H
KHRP26M33H
KHRP26M72H
KHRP26M73H+KHRP26M73HP
Refrigerant branch kit name
Example for indoor units
connected downstream
Example REFNET joint C : Indoor units 5 + 6 + 7 + 8
Example REFNET joint B : Indoor units 7 + 8
Example REFNET header : Indoor units 1 + 2 + 3 + 4 + 5 + 6
Example REFNET header :
Indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
Outdoor unit
REFNET joint (A~G)
First outdoor unit multi connection piping kit
Outdoor unit Outdoor unit
REFNET joint (A, B)
REFNET header
REFNET header
Equivalent pipe length between outdoor unit (*2) and indoor unit 150m (Note 1)
(Assume eqivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, that of BSVQ100, 160 to be 4m, that of BSVQ250 to be 6m for calculation purposes)
(In case of BSV4Q100PV1 and BSV6Q100PV1 (combined type BS unit), calculate at 4m per 1 unit.)
01_EN_3P226891_9.fm Page 12 Tuesday, December 1, 2009 4:38 PM