Specifications SiENBE37-701
24 Specifications
1-2 ELECTRICAL SPECIFICATIONS FXFQ20PVEB FXFQ25PVEB FXFQ32PVEB FXFQ40PVEB FXFQ50PVEB
Power
Supply
Name VE
Frequency Hz 50/60
Voltage V 220-240/220
Current Minimum circuit amps
(MCA)
A 0.4 0.4 0.4 0.5 0.6
Maximum fuse amps
(MFA)
A1616161616
Full load amps (FLA) A 0.3 0.3 0.3 0.4 0.5
Voltage
range
Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA <= 4 × FLA
next lower standard fuse rating minimum 16A
select wire size based on the MCA
instead of a fuse,use a circuit breaker
1-2 ELECTRICAL SPECIFICATIONS FXFQ63PVEB FXFQ80PVEB FXFQ100PVEB FXFQ125PVEB
Power
Supply
Name VE
Frequency Hz 50/60
Voltage V 220-240/220
Current Minimum circuit amps
(MCA)
A 0.9 0.9 1.4 1.9
Maximum fuse amps
(MFA)
A16161616
Full load amps (FLA) A 0.7 0.7 1.1 1.5
Voltage
range
Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA <= 4 × FLA
next lower standard fuse rating minimum 16A
select wire size based on the MCA
instead of a fuse, use a circuit breaker