Specifications SiENBE37-701
26 Specifications
1-1 TECHNICAL SPECIFICATIONS FXZQ20MV1B FXZQ25MV1B FXZQ32MV1B FXZQ40MV1B FXZQ50MV1B
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
1-2 ELECTRICAL SPECIFICATIONS FXZQ20MV1B FXZQ25MV1B FXZQ32MV1B FXZQ40MV1B FXZQ50MV1B
Power
Supply
Name V1
Phase 1 1 1 1 1
Frequency Hz 50 50 50 50 50
Voltage V 220-240
Current Minimum circuit amps
(MCA)
A 0.80 0.80 0.80 0.80 0.90
Maximum fuse amps
(MFA)
A 15.00 15.00 15.00 15.00 15.00
Full load amps (FLA) A 0.60 0.60 0.60 0.60 0.70
Voltage
range
Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA <= 4 × FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet. daikineurope.com, select "E-Data Books".