SiENBE37-701 Specifications
Specifications 37
1-1 TECHNICAL SPECIFICATIONS FXDQ20MV3B FXDQ25MV3B
Standard
Accessories
Standard Accessories Installation and operation manual
Fuse
Caution for servicing sticker
Suction air filter
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 8m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 8m, level difference : 0m.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
1-2 ELECTRICAL SPECIFICATIONS FXDQ20MV3B FXDQ25MV3B
Power
Supply
Name V1
Phase 1 1
Frequency Hz 50 50
Voltage V 230 230
Current Minimum circuit amps
(MCA)
A 0.20 0.20
Maximum fuse amps
(MFA)
A 16.00 16.00
Full load amps (FLA) A 0.10 0.10
Voltage
range
Minimum V -10%
Maximum V +10%
Power Supply Intake Both indoor and outdoor unit
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA < 4 × FLA
next lower standard fuse rating minimum 16A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".
Finally, click on the document title of your choice.