EasyManua.ls Logo

Daikin VRV III - Page 63

Daikin VRV III
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiENBE37-701 Specifications
Specifications 51
Floor Standing Unit
1-2 ELECTRICAL SPECIFICATIONS FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE
Power
Supply
Name VE
Phase 111111
Frequency Hz 50 50 50 50 50 50
Voltage V 220-240
Current Minimum circuit amps
(MCA)
A 0.30 0.30 0.60 0.60 0.60 0.60
Maximum fuse amps
(MFA)
A 15.00 15.00 15.00 15.00 15.00 15.00
Full load amps (FLA) A 0.20 0.20 0.50 0.50 0.50 0.50
Voltage
range
Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA <= 4 × FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".
Finally, click on the document title of your choice.

Other manuals for Daikin VRV III

Related product manuals