124 Cases for Examination
3.3 [Malfunction of Transmission Examples]
Faulty Condition to Multi-core Wire
Applicable
Models
VRV in general
Condition
Cause According to the wiring company, two-core lines were to be used as transmission line. However,
multi-core lines are used actually. There was also a case where two cores out of four cores
were being used for power supply.
Measure Request to correct the wiring.
Point of
Diagnosis
3.4 [Malfunction of Transmission Examples]
Faulty Condition Caused by the Use of Single-core Line
Applicable
Models
VRV in general
Condition
Cause A malfunction "U4" is issued due to a single-core line used as a transmission line.
Measure Changed to the VTCF two-core line.
Point of
Diagnosis