Field Settings for the Replacement of the Spare Control PC Board Si30-408
200 Appendix
2. RSXYP5, 8, 10L
In order to replace by the space PC board, change the setting of DIP switch (DS1) on the PC
board as shown below.
Default condition of DIP switch
3. RSXP16 ~ 30K, RSXYP16 ~ 30KJ, RSEYP16 ~ 30KJ
In order to replace by the space PC board,, change the setting of DIP switches (SS2 to SS5) on
the PC board as shown below.
Note: Resetting of power supply switch is neccessary after capacity setting.
5L 8L 10L
DS1-7 ON OFF ON
DS1-8 OFF ON ON
ON
OFF
1 2 3 4 5 6 7 8
DS1
SS2 SS3 SS4 SS5
ABCDEFGH
RSXYP16KJ
RSXP16K, RSEYP16KJ

RSXYP18KJ
RSXP18K, RSEYP18KJ

RSXYP20KJ
RSXP20K, RSEYP20KJ

RSXYP24KJ
RSXP24K, RSEYP24KJ

RSXYP26KJ
RSXP26K, RSEYP26KJ

RSXYP28KJ
RSXP28K, RSEYP28KJ

RSXYP30KJ
RSXP30K, RSEYP30KJ

Capacity setting table