Introduction
Function
The AK-PI 200 is an intermediary link allowing AKC and AKL type 
controllers to be operated via a system manager, e.g. AK-SM 720. 
The actual operation of the controllers is carried out with an AK-ST 
500.
(AKC and AKL controllers use the DANBUSS data communication 
system. The communication is controlled by a gateway, e.g. AKA 
245.
In a solution with an AK-PI 200 and a system manager, the 
gateway should not be used.)
Application
The AK-PI 200 is used on systems where the system unit is an 
AK-SM 720 and where there are one or more controllers with 
DANBUSS data communication. 
The unit links the communication to DANBUSS so that the system 
manager can present all the controllers on the system.
DANBUSS controllers are presented on an equal footing together 
with LON RS 485 controllers and MODBUS controllers.
All controllers can be viewed and operated from the system 
manager’s network overview.
The solution can be used on existing systems where the majority 
are DANBUSS controllers and where it would be desirable to 
change the system operation to a browser-based interface instead 
of an AKM software interface.
Or it can be used on new systems where the majority might be 
controllers with LON communication and other individual controls 
can be AKC controllers. 
Principle
The link between the system manager and the AK-PI 200 is via a 
TCP/IP. 
In this very simple connection the two units can be connected to 
each other via a crossed cable.
This is where the IP addresses are set to static addresses.
On larger systems or where there is also outgoing IP 
communication from the system, the connection must be made 
via a router.
Here the IP addresses can be dynamic, but if there is 
communication to the system from outside, they must be static.
If you are not sure whether you should select static or dynamic, abide 
by the following recommendation:
Dynamic is the easiest. Here the router itself allocates an address 
for the system manager and another for the PI unit. But you 
should only select this solution if the system is closed without a 
connection for an external operation interface.
With static you must obtain a couple of addresses yourself at the 
local IT department and you must also set the addresses yourself 
in the two units. This solution must always be used when the 
system is operated by an external service company, e.g. for log 
collection, alarm management or service. 
Contents
Introduction ....................................................................................................... 2
Installation
 .......................................................................................................... 4
Requirements and terms
 ............................................................................... 6
Ordering
 .............................................................................................................. 8
Data
 ....................................................................................................................... 8