6
Installation Guide  AME 335, AME 435
DH-SMT/SI  VI.LE.J1.3B  Danfoss Heating 
ENGLISH
Safety Note
To avoid injury and damage to persons 
and devices, it is absolutely necessary 
these instructions are carefully read 
and observed prior to assembly and 
commissioning.
Necessary assembly, start-up, and 
maintenance work must be performed 
only by qualied, trained and authorised 
personnel. 
Prior to assembly and maintenance work 
on the actuator, the system must be:
-  depressurised 
-  cooled down
-  emptied
-  cleaned
Please comply with the instructions of the 
system manufacturer or system operator.
Do not remove the cover 
before the power supply is fully 
switched o.
Disposal instruction
This product should be 
dismantled and its 
components sorted, if 
possible, in various groups 
before recycling or disposal. 
Always follow the local disposal 
regulations.
Mounting and installation ❶
Wiring ❷
Do not touch anything on the PCB!
Switch o the power line before wiring 
the actuator! Lethal voltage!
Wire the actuator according to the wiring 
diagram.
Functions accessible from cover
RESET ❸
By pushing STAND BY/RESET button for 
5 sec. the actuator starts self stroking 
procedure to adjust to the stroke of the 
valve to which it is connected.
Procedure starts with extracting the stem.
As the maximum force is detected 
the actuator reverse its direction until 
maximum force in opposite direction is 
detected.
During calibration Bi-Color LED blinks 
green 1/sec. After reaching fully upper end 
position actuator enter normal mode and 
start catching Y control signal.
Manual override ❹
NOTE: 
If manual override has been used then 
control and return signal are not correct until 
the actuator reaches its end position.
DIP switch settings ❺
Jumper ①: U/I - Input signal type selector 
DIP switches
Factory settings:
ALL switches are in OFF position! 
NOTE:
All combinations of DIP switches are allowed. 
All functions that are selected are added 
consecutively. 
SW 1: Not used
SW 2: 0/2 - Input signal range selector ②
SW 3: D/I - Direct or inverse acting 
selector③ 
SW 4: Fast/Slow: Speed selector ④
SW 5: Not used
SW 6: Not used
SW 7: LIN/MDF - Linear or modied ow 
characteristic ❻
SW 8: Smart function selector
If set on OFF position the actuator does 
not try to detect any oscillations in the 
system. If set on ON position actuator 
enables special anti oscillations algorithm.
LED function indicator ❼
Green – initialization (RESET), set-point 
position, transition indicator
Red - indicates STAND BY and Failure 
mode.
Green:
• Flashinglight(onceevery6sec.) ②
-  actuator reached set-point acc. to Y 
signal
• Nolight
-  no operation or no power supply
• Flashinglight(~1Hz)③
-  self adjusting mode.
Red:
• Nolight
-  no operation or no power supply
• Constantlight ④
-  fault condition occurred
• Flashinglight(2Hz) ①
-  STAND BY
-  power supply too low
-  initial self-adjusting time too short 
due to too short valve strokes
-   failure during self calibration.
Dismounting ❽