Important information 
Before the heat pump is supplied with voltage you must ensure that the heating system and coolant 
system are filled and bled of air otherwise the circulation pumps can be damaged.
If the electrician wishes to test his connections before the above is carried out, this should only done 
when it has been checked that the coolant pump, the condenser pump, the hot gas pump and the 
compressor are disconnected.
24 VAC 1 must not be connected together with:
• 24 VAC 2
• 24 VDC
• Other equipment that uses 0-10V control signal
• Signal ground GND
24 VAC 2 must only be used as power supply to:
• External equipment that requires 0-10V control 
  signal
• Auxiliary modules
The two separate 24 VAC circuits must never be connected to each other or to protective ground.
The total power load on 24 VAC 1 respectively 24 VAC 2 must not exceed 50VA.