Danfoss
60G456.10
Installation guide
Pressure transmitter
Type MBS 1700 and MBS 1750
© Danfoss A/S (IA-MS/IM) 2014-02 IC.PI.P20.U2.53 / 520B6098 1
060R9358
060R9358
Electrical connection:
4 – 20 mA output (2 wire)
Pin1: + supply
Pin 2: ÷ supply
Pin 3: Not used
Earth: Connected to MBS
enclosure
Guideline for temperature inuence
Medium temperature (t
m
), [°C] Heat isolator (L), [cm] Transmitter temperature (t
t
), [°C]
120
2 85
5 75
10 70
100
2 75
5 65
10 60
Question and Answer IconNeed help?

Do you have a question about the Danfoss MBS 1700 and is the answer not in the manual?

Danfoss MBS 1700 Specifications

General IconGeneral
TypePressure Transmitter
Output Signal4 - 20 mA
Accuracy±0.5% FS
Enclosure RatingIP65
MaterialStainless Steel
Operating Temperature-40°C to +85°C
Electrical ConnectionDIN 43650
Pressure ConnectionG 1/4
Storage Temperature-40 to 85°C

Summary

Electrical Connection

4-20 mA Output Wiring

Details the 2-wire 4-20 mA output connection with pin assignments for supply and earth.

Temperature Influence Guideline

Temperature Influence Table

Provides data on medium temperature, heat isolator length, and transmitter temperature.

Connector Handling Warning

Energized Connector Warning

Caution against removing the connector while the sensor is energized to prevent damage.